Sheet S-22 · Heating and cooling sizing
2000 sq ft, furnace + AC
- Heat loss
- 37,200BTU/h · rough
- Heat gain
- 26,100BTU/h · 2.2 tons
- Furnace
- 40kBTU/h input + 2.5-ton AC
- Supplies
- 145 returns
Tools you need
- Tape measure (25 ft)
- 4-ft level
- Cordless drill/driver
- Impact driver
- Aviation snips
- Oscillating multi-tool
31 tools on the Sheet, each marked own, buy or rent
| Buy | Item | How we got this |
|---|---|---|
| 1 furnace | Gas furnace, 40,000–45,000 BTU/h40,000 BTU/h input, 95%+ AFUE | Output ≈ 38,000 BTU/h (95% of input) for the 37,200 BTU/h heat loss: 102%. |
| 1 unit | AC condensing unit, 2.5–3 ton2.5 ton, A2L (R-454B or R-32) | 26,100 BTU/h heat gain ÷ 12,000 = 2.17 tons → 2.5 tons. |
| 1 coil | Evaporator coil, up to 3 ton2.5 ton, matched to the condenser | An AHRI-matched coil and condenser pair is what the efficiency rating (and many rebates) count. |
| 1 set | Line set (insulated copper pair)3/8 × 3/4 × 35′ | Coil to outdoor unit about 32 ft (across to the wall, out, to the unit, service loops). Factory charge covers about 15 ft: add about 10 oz (the R-410A figure; A2L units list theirs on the data plate). The unit’s instructions set the sizes. |
| 1 drier | Liquid-line filter drierliquid line | If the outdoor unit doesn’t ship with one. |
| 1 pack | Brazing rods, 15% silver | Line set joints, brazed with nitrogen flowing. |
| 6 sections | Rectangular trunk duct10×20 × 5′ | 27 ft of extended plenum along the house, sized for 1,000 CFM at about 800 ft/min. |
| 2 caps | Trunk end cap10×20 | Both ends of the trunk. |
| 1 plenum | Supply plenum | On the coil or air handler, feeding the trunk. |
| 1 plenum | Return plenum or return drop | Into the furnace or air handler, with the filter. |
| 14 take-offs | Round take-off with damper | 14 supply runs: the dampers balance the rooms. |
| 5 collars | Round start collar | 5 return runs into the return plenum: no damper on a return. |
| 13 bags | Insulated flex duct, 4–10 inch6″ R-6 × 25′ | 14 runs of about 21 ft (294 ft + 5%) in 25 ft bags; 70 CFM each is a 6″ run at about 0.1 in. w.c. per 100 ft. |
| 5 bags | Insulated flex duct, 4–10 inch8″ R-6 × 25′ | 3 bedroom returns, 102 ft in all. |
| 2 bags | Insulated flex duct, 12–16 inch12″ R-6 × 25′ | 2 central returns of 500 CFM, 37 ft to the return plenum (or panned joists and a sheet-metal drop instead). |
| 14 boots | Register boot4×10 × 6″ | One per supply. |
| 14 registers | Supply register4×10 | About one per 150 sq ft of floor, each about 70 CFM. |
| 2 grilles | Filter return grille20×20 | One central return per floor, each about 500 CFM through a 1-inch filter. |
| 3 grilles | Return grille10×10 | One per bedroom (4 people → 3 bedrooms), so closed doors don’t starve the room — or a jumper duct. |
| 4 gallons | Duct mastic1 gal | About 85 joints and seams, 25 to a gallon. |
| 2 rolls | UL 181 foil tape | Holds joints while the mastic cures; never cloth duct tape. |
| 1 pack | Flex duct clamps (pack)packs of 50 | Inner liner and jacket at both ends of every flex run. |
| 2 rolls | Duct hanger strap (100 ft)100′ roll | Supports every 4–5 ft, without pinching the duct. |
| 15 ft | Condensate line3/4 PVC | About 15 ft from the coil and the furnace to a drain or the pump. |
| 1 kit | Condensate fittings | A trap, a tee with a cleanout and the elbows. |
| 1 pump | Condensate pump | Unless a floor drain is within reach. |
| 38 ft | PVC DWV pipe, 2 in2″ Schedule 40 PVC, solid core | Vent and combustion-air pipes, about 19 ft each to the side wall. The furnace’s venting table sets the size and the longest run; no cellular-core pipe. |
| 1 kit | Vent termination kit2″ concentric or two-pipe | The furnace maker’s listed termination, with its clearances to windows, doors and the gas meter. |
| 1 kit | Vent fittings | Long-sweep elbows, couplings, hangers, primer and cement. |
| 1 valve | Gas appliance shutoff valve | Shutoff in the same room as the furnace. |
| 1 kit | Sediment trap and union | Drip leg and union at the furnace; the gas fitter sizes and pressure-tests the piping. |
| 2 alarms | Carbon monoxide alarm | One on each floor outside the sleeping areas: codes ask for them when a fuel-burning appliance goes in. Ask whether they must be hardwired. |
| 1 switch | Furnace service switch | Service switch at the furnace (on its own circuit). |
| 1 pad | Equipment pad | Level and a few inches above the ground (typical code wording: 3″). Confirm with your building department. |
| 1 set | Locking refrigerant caps (set) | Codes ask for tamper-resistant caps on refrigerant ports outdoors. |
| 1 refill | Dry nitrogen refill | Purge while brazing, then the pressure test before the vacuum. |
| 1 disconnect | AC disconnect, non-fused60 A, fused if the nameplate says so | Within sight of the outdoor unit (NEC 440.14). |
| 1 whip | AC whip, ¾-inch liquidtight, 6 ft | Disconnect to unit. |
| 1 breaker | Breaker, 2-poleper the nameplate MOP | Enter the nameplate MCA and MOP to size it. |
| 48 ft | NM cable 10/2 with ground10/2 with ground, typical — size it from the MCA | Panel to disconnect, about 48 ft — a guess: the panel’s place sets it. Cable inside; the electrician picks UF, conduit or a whip outside. |
| 1 thermostat | Thermostatheat and cool | One per system, on an inside wall away from supply registers and sun. |
| 29 ft | Thermostat wire18/5 | Equipment to thermostat, with a spare conductor or two and a C wire. |
| 37 ft | Thermostat wire18/2 | Along the line set to the outdoor unit. |
Sheet S-22 · Heating and cooling sizing
185.8 m², furnace + AC
- Heat loss
- 13.5kW · rough
- Heat gain
- 6.9kW · 2 tons
- Furnace
- 60kBTU/h input + 2-ton AC
- Supplies
- 145 returns
Tools you need
- Tape measure (7.5 m)
- 1.2 m level
- Cordless drill/driver
- Impact driver
- Aviation snips
- Oscillating multi-tool
31 tools on the Sheet, each marked own, buy or rent
| Buy | Item | How we got this |
|---|---|---|
| 1 furnace | Gas furnace, 60,000–70,000 BTU/h60,000 BTU/h input, 95%+ AFUE | Output ≈ 57,000 BTU/h (16.7 kW) (95% of input) for the 45,900 BTU/h (13.5 kW) heat loss: 124%. |
| 1 unit | AC condensing unit, 1.5–2 ton2 ton, A2L (R-454B or R-32) | 23,600 BTU/h (6.9 kW) heat gain ÷ 12,000 = 1.97 tons → 2 tons (7 kW). |
| 1 coil | Evaporator coil, up to 3 ton2 ton, matched to the condenser | An AHRI-matched coil and condenser pair is what the efficiency rating (and many rebates) count. |
| 1 set | Line set (insulated copper pair)3/8 × 3/4 × 10.67 m | Coil to outdoor unit about 9.75 m (across to the wall, out, to the unit, service loops). Factory charge covers about 4.57 m: add about 283 g (the R-410A figure; A2L units list theirs on the data plate). The unit’s instructions set the sizes. |
| 1 drier | Liquid-line filter drierliquid line | If the outdoor unit doesn’t ship with one. |
| 1 pack | Brazing rods, 15% silver | Line set joints, brazed with nitrogen flowing. |
| 6 sections | Rectangular trunk duct8×20 × 1.52 m | 8.26 m of extended plenum along the house, sized for 880 CFM (415 L/s) at about 4 m/s. |
| 2 caps | Trunk end cap8×20 | Both ends of the trunk. |
| 1 plenum | Supply plenum | On the coil or air handler, feeding the trunk. |
| 1 plenum | Return plenum or return drop | Into the furnace or air handler, with the filter. |
| 14 take-offs | Round take-off with damper | 14 supply runs: the dampers balance the rooms. |
| 5 collars | Round start collar | 5 return runs into the return plenum: no damper on a return. |
| 13 bags | Insulated flex duct, 4–10 inch6-inch R-6 × 7.62 m | 14 runs of about 6.40 m (89.61 m + 5%) in 7.62 m bags; 60 CFM (28 L/s) each is a 6-inch run at about 0.8 Pa per metre. |
| 5 bags | Insulated flex duct, 4–10 inch8-inch R-6 × 7.62 m | 3 bedroom returns, 31.09 m in all. |
| 2 bags | Insulated flex duct, 12–16 inch12-inch R-6 × 7.62 m | 2 central returns of 440 CFM (208 L/s), 11.28 m to the return plenum (or panned joists and a sheet-metal drop instead). |
| 14 boots | Register boot4×10 × 6-inch | One per supply. |
| 14 registers | Supply register4×10 | About one per 13.9 m² of floor, each about 60 CFM (28 L/s). |
| 2 grilles | Filter return grille14×20 | One central return per floor, each about 440 CFM (208 L/s) through a 1-inch filter. |
| 3 grilles | Return grille10×10 | One per bedroom (4 people → 3 bedrooms), so closed doors don’t starve the room — or a jumper duct. |
| 15.1 L | Duct mastic3.8 L | About 85 joints and seams, 25 to a gallon. |
| 2 rolls | UL 181 foil tape | Holds joints while the mastic cures; never cloth duct tape. |
| 1 pack | Flex duct clamps (pack)packs of 50 | Inner liner and jacket at both ends of every flex run. |
| 2 rolls | Duct hanger strap (30.48 m)30.48 m roll | Supports every 1.22–1.52 m, without pinching the duct. |
| 4.57 m | Condensate line3/4 PVC | About 4.57 m from the coil and the furnace to a drain or the pump. |
| 1 kit | Condensate fittings | A trap, a tee with a cleanout and the elbows. |
| 1 pump | Condensate pump | Unless a floor drain is within reach. |
| 11.58 m | Plastic vent pipe, ULC S6362-inch System 636 | Vent and combustion-air pipes, about 5.79 m each to the side wall. The furnace’s venting table sets the size and the longest run. |
| 1 kit | Vent termination kit2-inch concentric or two-pipe | The furnace maker’s listed termination, with its clearances to windows, doors and the gas meter. |
| 1 kit | Vent fittings | Long-sweep elbows, couplings, hangers, primer and cement. |
| 1 valve | Gas appliance shutoff valve | Shutoff in the same room as the furnace. |
| 1 kit | Sediment trap and union | Drip leg and union at the furnace; the gas fitter sizes and pressure-tests the piping. |
| 2 alarms | Carbon monoxide alarm | One on each floor outside the sleeping areas: codes ask for them when a fuel-burning appliance goes in. Ask whether they must be hardwired. |
| 1 switch | Furnace service switch | Service switch at the furnace (on its own circuit). |
| 1 pad | Equipment pad | Level and a few inches above the ground (typical code wording: 76 mm). Confirm with your building department. |
| 1 set | Locking refrigerant caps (set) | Codes ask for tamper-resistant caps on refrigerant ports outdoors. |
| 1 refill | Dry nitrogen refill | Purge while brazing, then the pressure test before the vacuum. |
| 1 disconnect | AC disconnect, non-fused60 A, fused if the nameplate says so | Within sight of the outdoor unit (Canadian Electrical Code). |
| 1 whip | AC whip, ¾-inch liquidtight, 1.83 m | Disconnect to unit. |
| 1 breaker | Breaker, 2-poleper the nameplate MOP | Enter the nameplate MCA and MOP to size it. |
| 14.63 m | NM cable 10/2 with ground10/2 with ground, typical — size it from the MCA | Panel to disconnect, about 14.63 m — a guess: the panel’s place sets it. Cable inside; the electrician picks UF, conduit or a whip outside. |
| 1 thermostat | Thermostatheat and cool | One per system, on an inside wall away from supply registers and sun. |
| 8.84 m | Thermostat wire18/5 | Equipment to thermostat, with a spare conductor or two and a C wire. |
| 11.28 m | Thermostat wire18/2 | Along the line set to the outdoor unit. |